The IPAC2000 series of regenerative AC electronic loads are used for generators, AC sources, inverters, UPS/EPS, charging piles, controllers and switch segment devices, server AC devices, power electronic equipment testing and aging. The AC feedback electronic load is a power electronic conversion device based on a two-stage conversion architecture of power frequency isolated IGBT rectification and inverter. It has high reliability and programmability; it can realize local control through internal control and communication modules And remote control. The internal sampling circuit can quickly detect over current, overload, over voltage and output short circuit, and automatically protect and cut off the output, and send out an alarm. The power inverter unit uses integrated laminated busbar technology and modular configuration to improve quality reliability and stability. The equipment adopts touch screen display and control, and the operation is simpler。
◆ Using the principle of PWM rectification + PWM inverter, it can realize energy feedback to the grid, and has outstanding advantages such as energy saving and consumption reduction, and green environmental protection.
◆ The PF value can be set between 0.3 and 1 (leading or lagging).
◆ It has a wide voltage input range and a wide frequency input range.
◆ With constant resistance, constant current, and constant power working modes.
◆ Using PWM synchronous rectification, combined with software algorithm PFC correction control, to achieve power factor (PF) ≥ 0.99.
◆ ITHD≤3%.
◆ It has complete grid-connected protection functions: over frequency, under frequency, over voltage, under voltage, overload, etc. To
◆ Three-phase has three-phase independent adjustable function, (harmonic adjustment option).
Model number
|
IPAC2000 series regenerative AC electronic load
|
capacity
|
1KW-1500KW optional
|
AC input
|
Number of phases
|
3φ4W+PE Three-phase four-wire (three-wire) + ground wire or 1φ2W+PE single-phase two-wire + ground wire (power supply)
|
voltage range
|
50V-650V
|
Current range
|
0-3000A
|
Frequency
|
43Hz – 67 Hz
|
Power Factor
|
0.3~1 (leading, lagging)
|
Current harmonics
|
<3% (rated power)
|
Loadcharacteristics
|
mode
|
Constant current, constant resistance, constant power
|
Constant power accuracy
|
≤±0.8 % FS
|
Constantcurrent accuracy
|
≤±0.6 % FS
|
Constant resistance accuracy
|
≤±0.6 % FS
|
Time accuracy
|
Setting 0.1 sec+ 0.1 %
|
Harmonics editor
|
Can edit any harmonic 2-50 times (optional function)
|
Voltage resolution
|
0.1V
|
Current resolution
|
0.01A
|
protect
|
Phase loss, overvoltage, overcurrent, overtemperature, overload, short circuit, reverse connection
|
cooling method
|
Forced air cooling
|
responding speed
|
<10ms
|
Power supply
|
380VAC ±15% 50HZ/220VAC±50HZ
|
show
|
touch screen
|
Communication Interface
|
RS485/LAN
|
Insulation resistance
|
Input to the chassis 20MΩ 500VDC, output to the chassis 20MΩ 500VDC
|
Withstand voltage
|
Input to chassis 1500VAC for 1 minute, input to output 1500VAC for 1 minute
|
Feedback characteristics
|
Rated output voltage
|
380V AC/220VAC 50HZ/60HZ (three-phase is three-phase feeder network, single-phase is single-phase feeder network)
|
Total current distortion distortion T.H.D
|
<3%
|
Output frequency
|
50Hz/60Hz
|
Output overvoltage protection
|
>418V AC
|
Output undervoltage protection
|
<342V AC
|
Feedback power
|
100% full scale power feedback
|
other
|
Operating environment
|
0 – 45℃ (outdoor/-20℃ 50℃ need to be customized) 10-90%RH
|
cooling method
|
Air-cooled
|
noise
|
<60dB
|
Protection level
|
IP30
|